[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-936150":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},936150,605,2,"多选题","采用气体灭火系统灭火后的防护区应通风换气，下列关于通风换气的相关设置或设施的说法符合规定的有（ ）",[11,15,18,22,25],{"key":12,"text":13,"correct":14},"A","地下防护区和无窗的地上防护区应设置机械排风装置",true,{"key":16,"text":17,"correct":14},"B","电子计算机房的通风换气次数应不小于每小时5次",{"key":19,"text":20,"correct":21},"C","排风口宜设在防护区的上部并应直通室外",false,{"key":23,"text":24,"correct":21},"D","通信机房的通风换气次数应不小于每小时4次",{"key":26,"text":27,"correct":21},"E","设固定窗扇的地上防护区可不设机械排风装置","AB","灭火后的防护区应通风换气，地下防护区和无窗或固定窗扇的地上防护区应设置机械排风装置，排风口宜设在防护区的下部并直通室外。通信机房、电子计算机房等场所的通风换气次数应不小于每小时5次。",{"id":6,"name":31,"category":32,"favorite":33},"消防技术综合能力(一级、二级)","建筑工程",0]