[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-936149":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},936149,605,2,"多选题","某学校电子计算机房共十个防护区，层高为4．5m，其中有两个防护区有地板层，地板层高度为300mm，采用组合分配式七氟丙烷气体灭火系统，下列检查结果，不符合规范要求的是（ ）。",[11,15,18,22,25],{"key":12,"text":13,"correct":14},"A","共设置两套组合分配系统，集流管分别设置，其中一个集流管上的所用90L钢瓶10组，120L钢瓶2组",true,{"key":16,"text":17,"correct":14},"B","地板下设置喷头的保护半径为5m",{"key":19,"text":20,"correct":21},"C","防护区的泄压口高度均在距地3．5m处",false,{"key":23,"text":24,"correct":14},"D","灭火剂输送DN25管道的管道支架间距为2．5m",{"key":26,"text":27,"correct":14},"E","防护区入口处的手自动转换开关，安装高度距地1．7m","ABDE","A错，同一集流管上的储存容器，其规格、充压压力和充装量应相同。B错误，地板下喷头安装高度小于1.5m，保护半径不宜大于4．5m，5m不满足要求。C正确，防护区应设置泄压口，七氟丙烷灭火系统的泄压口应位于防护区净高的2／3以上。D错，DN25的灭火剂输送管道，管道支架最大间距为2．1m。E错，设置在防护区处的手动、自动转换开关应安装在防护区入口便于操作的部位，安装高度为中心点距地（楼）面1．5m。",{"id":6,"name":31,"category":32,"favorite":33},"消防技术综合能力(一级、二级)","建筑工程",0]