[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-936135":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":16,"analysis":25},936135,605,1,"单选题","对安装完毕的气体灭火系统进行检查，检查结果如下，其中不符合相应规范要求的是（ ）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","管道末端的防晃支架与末端喷嘴间的距离为30cm",false,{"key":16,"text":17,"correct":18},"B","穿楼板套管的长度高出楼板30mm",true,{"key":20,"text":21,"correct":14},"C","选择阀上有标明保护对象的永久性标志牌，并便于观察",{"key":23,"text":24,"correct":14},"D","气体喷放指示灯安装在防护区入口的正上方","根据《气体灭火系统施工及验收规范》GB 50263—20075．5．3—2，管道末端应采用防晃支架固定，支架与末端喷嘴间的距离不应大于500 mm，A选项正确；根据5．5．2，穿墙套管长度应与墙厚相等，穿楼板套管长度应高出地板50mm，B选项错误；根据5．3．4，选择阀上应设置标明防护区或保护对象名称或编号的永久性标志牌，并应便于观察，C选项正确；根据5．8．4，气体喷放指示灯宜安装在防护区入口的正上方，D选项正确。本题答案为B。",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]