[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-936121":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":16,"analysis":25},936121,605,1,"单选题","对气体灭火系统的外观检查中，不符合要求的是（ ）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","同一规格的灭火剂储存容器，其高度差为15 mm",false,{"key":16,"text":17,"correct":18},"B","同一规格的驱动气体储存容器，其高度差为15 mm",true,{"key":20,"text":21,"correct":14},"C","球阀或蝶阀结构的总控阀标有阀位指示标志（“开”和“关”或者“OPEN”和“CLOSE”），指示标志清晰易见",{"key":23,"text":24,"correct":14},"D","组件所有外露接口均设有防护堵盖，且封闭良好，接口螺纹和法兰密封面无损伤","气体灭火系统组件的外观质量要求：（1）系统组件应无碰撞变形及其他机械性损伤。（2）组件外露非机械加工表面保护涂层完好。（3）组件所有外露接口均设有防护堵盖，且封闭良好，接口螺纹和法兰密封面无损伤。（4）储存容器外表正面标注灭火剂名称，字迹明显、清晰，标志铭牌牢固且设置在系统明显部位，选择阀、单向阀标有介质流动方向的标志。（5）球阀或蝶阀结构的总控阀标有阀位指示标志（“开”和“关”或者“OPEN”和“CLOSE”），指示标志清晰易见；利用手轮开启的阀门，在手轮上标有开关方向。（6）同一规格的灭火剂储存容器，其高度差不宜超过20 mm。（7）同一规格的驱动气体储存容器，其高度差不宜超过10 mm。",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]