[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-936115":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":16,"analysis":25},936115,605,1,"单选题","下列关于气体灭火系统中气动驱动装置管道安装的说法，错误的是（ ）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","气动驱动装置水平管道应采用管卡固定",false,{"key":16,"text":17,"correct":18},"B","气动驱动装置水平管道管卡的间距不宜大于0．8m",true,{"key":20,"text":21,"correct":14},"C","气动驱动装置竖直管道应在其始端和终端设防晃支架或采用管卡固定",{"key":23,"text":24,"correct":14},"D","气动驱动装置水平管道转弯处应增设1个管卡","根据《气体灭火系统施工及验收规范》GB 50263—20075．4．5，气动驱动装置的管道安装应符合下列规定： 1）管道布置应符合设计要求。 2）竖直管道应在其始端和终端设防晃支架或采用管卡固定。 3）水平管道应采用管卡固定，管卡的间距不宜大于0．6m，转弯处应增设1个管卡。",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]