[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-936111":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},936111,605,2,"多选题","某单位设安装的气体灭火系统安装调试完毕后，委托消防设施检测机构进行技术检测。关于气体灭火系统检测的下列说法中，错误的有（ ）。",[11,15,19,22,25],{"key":12,"text":13,"correct":14},"A","储存容器的规格和效量应符合设计文件要求，且同一系统的储存容器的规格、尺寸要一致，其高度差不应超过10mm",true,{"key":16,"text":17,"correct":18},"B","储存容器必须固定在支架上，操作面距墙或操作面之间的距离应不小于1.0m，且不小于储存容器外径的1.5倍",false,{"key":20,"text":21,"correct":14},"C","灭火剂储存容器的充装量和储存压力应符合设计文件，且不超过设计充装量的3%",{"key":23,"text":24,"correct":14},"D","容器阀和集流管之间采用刚性连接",{"key":26,"text":27,"correct":14},"E","储存容器中充装的二氧化碳质量损失大于15%时，二氧化碳灭火系统的检漏装置应正确报警","ACDE","选项A，高度差不应超过20mm。选项C，不超过设计充装量的1.5%。选项D，应采用挠性连接。选项E，损失大于10%时应正确报警。",{"id":6,"name":31,"category":32,"favorite":33},"消防技术综合能力(一级、二级)","建筑工程",0]