[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-936104":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":22,"analysis":25},936104,605,1,"单选题","某防护区采用高压二氧化碳气体灭火系统进行保护，该防护区灭火剂输送管道采用气压强度试验代替水压强度试验时，最小试验压力应为（ ）MPa。",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","4",false,{"key":16,"text":17,"correct":14},"B","3．2",{"key":19,"text":20,"correct":14},"C","15",{"key":22,"text":23,"correct":24},"D","12",true,"根据《气体灭火系统施工及验收规范》GB 50263—2007 E．1．3，当水压强度试验条件不具备时，可采用气压强度试验代替。气压强度试验压力取值：二氧化碳灭火系统取80％水压强度试验压力，根据E．1．1-1，水压强度试验压力对高压二氧化碳灭火系统，应取15．0 MPa；对低压二氧化碳灭火系统，应取4．0 MPa，15×0．8=12MPa。本题答案为D。",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]