[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-936093":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":12,"analysis":25},936093,605,1,"单选题","细水雾灭火系统管道穿越楼板时应加设套管，套管的长度应高出楼地面（ ）mm。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","50",true,{"key":16,"text":17,"correct":18},"B","70",false,{"key":20,"text":21,"correct":18},"C","100",{"key":23,"text":24,"correct":18},"D","120","根据《细水雾灭火系统技术规范}GB 50898—20134．3．7—4，管道穿越墙体、楼板处应使用套管；穿过墙体的套管长度不应小于该墙体的厚度，穿过楼板的套管长度应高出楼地面50mm，管道与套管间的空隙应采用防火封堵材料填塞密实。设置在有爆炸危险场所的管道应采取导除静电的措施。本题答案为A。",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]