[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-936088":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},936088,605,2,"多选题","细水雾灭火系统是一种灭火效能高、环保、使用范围较广的灭火系统。在对细水雾灭火系统的管网试压试验中，以下试验条件或操作符合规范要求的有（ ）。",[11,15,19,22,25],{"key":12,"text":13,"correct":14},"A","水压试验环境温度应不低于0℃，当低于0℃时，应采取防冻措施",false,{"key":16,"text":17,"correct":18},"B","试验压力为系统工作压力的1．5倍",true,{"key":20,"text":21,"correct":18},"C","试验用水的水质与管道的冲洗水一致，水中氯离子含量不超过25 mg／kg",{"key":23,"text":24,"correct":14},"D","试验的测试点设在系统管网的最高点",{"key":26,"text":27,"correct":14},"E","当压力升至试验压力后，稳压5 min，管道无损坏、变形，再将试验压力降至设计压力，稳压90min","BC","细水雾灭火系统管网水压试验条件：（1）环境温度不低于5℃，当低于5℃时，采取防冻措施，以确保水压试验正常进行。（2）试验压力为系统工作压力的1．5倍。（3）试验用水的水质与管道的冲洗水一致，水中氯离子含量不超过25 mg／kg。试验要求：试验的测试点宜设在系统管网的最低点。管网注水时，将管网内的空气排净，缓慢升压。当压力升至试验压力后，稳压5 min，管道无损坏、变形，再将试验压力降至设计压力，稳压120min。",{"id":6,"name":31,"category":32,"favorite":33},"消防技术综合能力(一级、二级)","建筑工程",0]