[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-936078":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},936078,605,1,"单选题","细水雾灭火系统管道冲洗合格后，应进行压力试验，按照规范，下列说法正确的是（ ）。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","当压力升至试验压力后，稳压2min，管道无损坏、变形，再将试验压力降至设计压力，稳压60min",false,{"key":16,"text":17,"correct":14},"B","当压力升至试验压力后，稳压2min，管道无损坏、变形，再将试验压力降至设计压力，稳压120min",{"key":19,"text":20,"correct":21},"C","当压力升至试验压力后，稳压5min，管道无损坏、变形，再将试验压力降至设计压力，稳压120min",true,{"key":23,"text":24,"correct":14},"D","当压力升至试验压力后，稳压5min，管道无损坏、变形，再将试验压力降至设计压力，稳压60min","根据《细水雾灭火系统技术规范》GB 50898—20134．3．9，管道冲洗合格后，管道应进行压力试验，试验方法为管道充满水、排净空气，用试压装置缓慢升压，当压力升至试验压力后，稳压5min，管道无损坏、变形，再将试验压力降至设计压力，稳压120min，以压力不降、无渗漏、目测管道无变形为合格。本题答案为C。",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]