[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-936071":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},936071,605,2,"多选题","下列属于水喷雾灭火系统月度检查项目的有（ ）。",[11,15,19,22,25],{"key":12,"text":13,"correct":14},"A","电磁阀的启动测试",true,{"key":16,"text":17,"correct":18},"B","消防水泵自动控制启动测试",false,{"key":20,"text":21,"correct":18},"C","水源控制阀外观检查",{"key":23,"text":24,"correct":14},"D","手动控制阀门的铅封、锁链检查",{"key":26,"text":27,"correct":18},"E","系统放水测试","AD","根据《水喷雾灭火系统技术规范》GB 50219—201410．0．6—1，每月应检查电磁阀并进行启动试验，动作失常时应及时更换，A选项正确；根据10．0．5，每周应对消防水泵和备用动力进行一次启动试验。当消防水泵为自动控制启动时，应每周模拟自动控制的条件启动运转一次，B选项错误；根据10．0．4—1，每日应对水源控制阀、雨淋报警阀进行外观检查，阀门外观应完好，启闭状态应符合设计要求，C选项错误；根据10．0．6—2，每月应检查手动控制阀门的铅封、锁链，当有破坏或损坏时应及时修理更换，D选项正确；根据10．0．7—1，每季度应对系统进行一次放水试验，检查系统启动、报警功能以及出水情况是否正常，E选项错误。本题答案为AD。",{"id":6,"name":31,"category":32,"favorite":33},"消防技术综合能力(一级、二级)","建筑工程",0]