[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-936070":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},936070,605,2,"多选题","下列关于水喷雾灭火系统调试方法的说法中，正确的有（ ）。",[11,15,18,22,25],{"key":12,"text":13,"correct":14},"A","报警阀调试应采用工作管道进行",false,{"key":16,"text":17,"correct":14},"B","自动和手动方式启动的雨淋阀，应在30s之内启动",{"key":19,"text":20,"correct":21},"C","公称直径大于200mm的报警阀调试时，应在60s之内启动",true,{"key":23,"text":24,"correct":21},"D","报警阀调试时，当报警水压为0．05MPa，水力警铃应发出报警铃声",{"key":26,"text":27,"correct":21},"E","调试过程中，系统排出的水应通过排水设施全部排走","CDE","系统调试方法： 1）报警阀调试宜利用检测、试验管道进行。自动和手动方式启动的雨淋阀，应在15s之内启动：公称直径大于200mm的报警阀调试时，应在60s之内启动；报警阀调试时，当报警水压为0．05MPa，水力警铃应发出报警铃声。 2）水喷雾系统的联动试验，可采用专用测试仪表或其他方式。对火灾自动报警系统的各种探测器输入模拟火灾信号，火灾自动报警控制器应发出声光报警信号并启动水喷雾灭火系统。采用传动管启动的水喷雾系统联动试验时，启动一只喷头或试水装置，雨淋阀打开，压力开关动作，水泵启动。 3）调试过程中，系统排出的水应通过排水设施全部排走。 本题答案为CDE。",{"id":6,"name":31,"category":32,"favorite":33},"消防技术综合能力(一级、二级)","建筑工程",0]