[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-936069":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},936069,605,1,"单选题","下列关于自动喷水灭火系统报警阀组安装要求的说法中，不符合现行国家消防技术标准的是（ ）。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","报警阀组的安装应在供水管网试压、冲洗合格后进行",false,{"key":16,"text":17,"correct":14},"B","报警阀组的安装顺序应为水源控制阀、报警阀、报警阀辅助管道",{"key":19,"text":20,"correct":21},"C","当设计无要求时，报警阀组应安装在便于操作的明显位置，距室内地面高度宜为0.7m",true,{"key":23,"text":24,"correct":14},"D","安装报警阀组的室内地面应有排水设施","《自动喷水灭火系数施工及验收规范》（GB 50261-2005），5.3.1，当设计无要求时，报警阀组应安装在便于操作的明显位置，距室内地面高度宜为1.2m。",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]