[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-936065":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":22,"analysis":25},936065,605,1,"单选题","水喷雾灭火系统的阀门在进场检验时应进行强度和严密性试验，其中强度试验压力应为公称压力的（ ）倍，严密性试验压力应为公称压力的（ ）倍。",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","1．2，1．1",false,{"key":16,"text":17,"correct":14},"B","1．5，1．2",{"key":19,"text":20,"correct":14},"C","1．2，1．0",{"key":22,"text":23,"correct":24},"D","1．5，1．1",true,"根据《水喷雾灭火系统技术规范》GB 50219—20148．2．9，阀门的强度和严密性试验应采用清水进行，强度试验压力应为公称压力的1．5倍，严密性试验压力应为公称压力的1．1倍。本题答案为D。",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]