[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-936055":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},936055,605,1,"单选题","在水喷雾灭火系统报警阀组的安装过程中，不符合国家工程消防技术标准的做法是（ ）。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","安装位置靠近保护对象附近，并便于操作",false,{"key":16,"text":17,"correct":14},"B","距室内地面高度为1．2 m，两侧与墙的距离为0．6 m，正面与墙的距离为1．2m",{"key":19,"text":20,"correct":21},"C","报警阀组凸出部位之间的距离为0．4 m",true,{"key":23,"text":24,"correct":14},"D","安装报警阀组的室内地面设有排水设施","水喷雾灭火系统的报警阀组安装前应对供水管网试压、冲洗合格。安装顺序为：先安装水源控制阀、报警阀，然后进行报警阀辅助管道的连接，水源控制阀、报警阀与配水干管的连接，应使水流方向一致。报警阀组安装的位置应符合设计要求；当设计无要求时，宜靠近保护对象附近并便于操作的地点。距室内地面高度宜为1．2m，两侧与墙的距离不应小于0．5 m，正面与墙的距离不应小于1．2 m。报警阀组凸出部位之间的距离不应小于0．5 m，安装报警阀组的室内地面应有排水设施。",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]