[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-936045":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},936045,605,2,"多选题","对自动喷水灭火系统的报警阀组进行检查，根据现行国家标准《自动喷水灭火系统施工及验收规范》GB 50261—2017，下列关于报警阀组的安装要求的说法中，正确的是（ ）。",[11,15,19,22,25],{"key":12,"text":13,"correct":14},"A","干式报警阀的安全排气阀应安装在气源与报警阀之间，且应靠近气源",false,{"key":16,"text":17,"correct":18},"B","湿式报警阀报警水流通路上的过滤器应安装在延迟器前，且便于排渣操作的位置",true,{"key":20,"text":21,"correct":18},"C","干式报警阀安装完成后，应向报警阀气室注入高度为50mm～100mm的清水",{"key":23,"text":24,"correct":18},"D","水源控制阀安装应便于操作，且应有明显开闭标志和可靠的锁定设施",{"key":26,"text":27,"correct":14},"E","干式报警阀的低气压预报警装置应安装在供水干管一侧","BCD","根据《自动喷水灭火系统施工及验收规范》GB 50261—20175．3．4—5，干式报警阀的安全排气阀应安装在气源与报警阀之间，且应靠近报警阀，A选项错误；根据5．3．3—2，湿式报警阀报警水流通路上的过滤器应安装在延迟器前，且便于排渣操作的位置，B选项正确；根据5．3．4—2，干式报警阀安装完成后，应向报警阀气室注入高度为50mm～100mm的清水，C选项正确；根据5．3．2—3，水源控制阀安装应便于操作，且应有明显开闭标志和可靠的锁定设施，D选项正确；根据5．3．4—7，干式报警阀的低气压预报警装置应安装在配水干管一侧，E选项错误。本题答案为BED。",{"id":6,"name":31,"category":32,"favorite":33},"消防技术综合能力(一级、二级)","建筑工程",0]