[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-936044":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},936044,605,2,"多选题","根据现行国家标准《自动喷水灭火系统施工及验收规范》GB 50261—2017，对自动喷水灭火系统的报警阀组进行验收，下列报警阀组动作的说法，正确的是（ ）。",[11,15,19,22,25],{"key":12,"text":13,"correct":14},"A","雨淋报警阀动作后15s内压力开关应动作",true,{"key":16,"text":17,"correct":18},"B","雨淋报警阀动作后60s内压力开关应动作",false,{"key":20,"text":21,"correct":18},"C","打开末端试（放）水装置，当流量达到报警阀动作流量时，湿式报警阀和压力开关应及时动作，不带延迟器的报警阀应在60s内压力开关动作",{"key":23,"text":24,"correct":14},"D","测试水力警铃时，水力警铃喷嘴处压力不应小于0．05MPa",{"key":26,"text":27,"correct":14},"E","打开末端试（放）水装置，当流量达到报警阀动作流量时，湿式报警阀不带延迟器的报警阀应在15 s内压力开关动作","ADE","根据《自动喷水灭火系统施工及验收规范》GB 50261—20178．0．7—7，打开末端试（放）水装置，当流量达到报警阀动作流量时，湿式报警阀和压力开关应及时动作，带延迟器的报警阀应在90s内压力开关动作，不带延迟器的报警阀应在15s内压力开关动作；雨淋报警阀动作后15s内压力开关动作，AE选项正确，BC选项错误，根据8．0．7—3，水力警铃的设置位置应正确，测试时，水力警铃喷嘴处压力不应小于0．05MPa，且距水力警铃3m远处警铃声声强不应小于70dB，D选项正确。本题答案为ADE。",{"id":6,"name":31,"category":32,"favorite":33},"消防技术综合能力(一级、二级)","建筑工程",0]