[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-936039":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},936039,605,1,"单选题","下列关于水泵接合器的说法中，不正确的是（ ）。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","建筑高度为 32m 的公共建筑应设置水泵接合器",false,{"key":16,"text":17,"correct":14},"B","建筑高度为 33m 的住宅建筑应设置水泵接合器",{"key":19,"text":20,"correct":21},"C","建筑层数为 4 层层高为 5m 的丁类厂房应设置水泵接合器",true,{"key":23,"text":24,"correct":14},"D","建筑层数为 5 层层高为 5m 的丙类厂房应设置水泵接合器","高层民用建筑、设有消防给水的住宅、超过五层的其他多层民用建筑、超过两层或建筑面积大于10000平方米的地下或半地下建筑（室）、室内消火栓设计流量大于 10 L\u002Fs 平战结合的人防工程、高层工业建筑和超过四层的多层工业建筑、城市交通隧道，其室内消火栓给水系统 应设水泵接合器;自动喷水灭火系统、水喷雾灭火系统、泡沫灭火系统和固定消防炮灭火系统等水灭火系统，均应设置消防水泵接合器。",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]