[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-936037":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":22,"analysis":25},936037,605,1,"单选题","下列关于自动喷水灭火系统报警阀组的设置要求中，正确的是（ ）。",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","对于干式系统，一个报警阀组控制的喷头数不宜超过800个",false,{"key":16,"text":17,"correct":14},"B","对于预作用系统，一个报警阀组控制的喷头数不宜超过500个",{"key":19,"text":20,"correct":14},"C","报警阀组的报警管路总长度不宜大于30m",{"key":22,"text":23,"correct":24},"D","每个报警阀组供水的最高和最低位置的喷头高程差不宜大于50m",true,"根据《自动喷水灭火系统设计规范》GB 50084—20176．2．3，一个报警阀组控制的洒水喷头数，湿式系统、预作用系统不宜超过800只，干式系统不宜超过500只，AB选项错误；根据6．2．8，与报警阀连接的管道，其管径应为20mm，总长不宜大于20m，C选项错误；根据6。2．4，每个报警阀组供水的最高与最低位置洒水喷头，其高程差不宜大于50m，D选项正确。本题答案为D。",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]