[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-936032":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":22,"analysis":25},936032,605,1,"单选题","下列关于自动喷水灭火系统周期性维护管理的说法中，正确的是（ ）。",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","每季度对所有的末端试水阀和报警阀的放水实验阀进行一次放水实验，并应检查系统的压力是否正常",false,{"key":16,"text":17,"correct":14},"B","每季度对所有的末端试水阀和报警阀的放水实验阀进行一次放水实验，并应检查系统的出水情况是否正常",{"key":19,"text":20,"correct":14},"C","每季度对所有的末端试水阀和报警阀的放水实验阀进行一次放水实验，并应检查系统的严密性是否正常",{"key":22,"text":23,"correct":24},"D","每季度对所有的末端试水阀和报警阀的放水实验阀进行一次放水实验，并应检查系统的启动、报警功能以及出水情况是否正常",true,"《自动喷水灭火系统施工及验收规范》（GB 50261-2005），9.0.6，每个季度应对系统所有的末端试水阀和报警阀旁的放水试验阀进行一次放水试验，检查系统启动、报警功能以及出水情况是否正常。",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]