[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-936028":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":12,"analysis":25},936028,605,1,"单选题","下列有关水力警铃安装要求的说法，不正确的是（ ）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","水力警铃应安装在消防控制室或值班室附近的外墙上",true,{"key":16,"text":17,"correct":18},"B","水力警铃应安装检修、测试用的阀门",false,{"key":20,"text":21,"correct":18},"C","水力警铃和报警阀之间应采用热镀锌钢管连接",{"key":23,"text":24,"correct":18},"D","水力警铃启动时，警铃声强度应不小于70dB","根据《自动喷水灭火系统施工及验收规范》GB 50261—20175．4．4，水力警铃应安装在公共通道或值班室附近的外墙上，且应安装检修、测试用的阀门。水力警铃和报警阀的连接应采用热镀锌钢管，当镀锌钢管的公称直径为20mm时，其长度不宜大于20m；安装后的水力警铃启动时，警铃声强度应不小于70dB。本题答案为A。",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]