[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-936005":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},936005,605,2,"多选题","对某商场设置的湿式自动喷水灭火系统进行年度检测。打开末端试水装置，水流指示器动作、压力开关动作、消防水泵启动、水力警铃报警。检查发现末端试水装置出水压力为 0.05MPa ，但水力警铃不能持续报警，下列关于水力警铃不能持续报警的原因分析，正确的是（ ）。",[11,15,19,22,25],{"key":12,"text":13,"correct":14},"A","水力警铃安装调试不符合要求",true,{"key":16,"text":17,"correct":18},"B","延迟器下部的出水孔被堵塞",false,{"key":20,"text":21,"correct":14},"C","产品质量问题",{"key":23,"text":24,"correct":14},"D","水力警铃铃锤机构被卡住",{"key":26,"text":27,"correct":18},"E","水泵供水压力不足","ACD","水力警铃工作不正常（不响、响度不够、不能持续报警） （1）故障原因分析。 1）产品质量问题或者安装调试不符合要求。 2） 报警阀至水力警铃的管路阻塞或者铃锤机构被卡住。本题答案为ＡＣ",{"id":6,"name":31,"category":32,"favorite":33},"消防技术综合能力(一级、二级)","建筑工程",0]