[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-936004":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},936004,605,2,"多选题","对不同类型喷头进行安装时，安装方式正确的包括（ ）。",[11,15,18,21,24],{"key":12,"text":13,"correct":14},"A","隐蔽式喷头安装时，喷头根部螺纹及其部分或者全部本体嵌入顶棚护罩内，喷头下垂安装于配水支管上",true,{"key":16,"text":17,"correct":14},"B","干式喷头连接于特殊的短立管上，根据其保护区域结构特征和喷头型号、规格，直立向上、下垂或者水平安装于配水支管上",{"key":19,"text":20,"correct":14},"C","齐平式喷头安装时，喷头根部螺纹及其部分本体下垂安装于顶棚内配水支管上，部分或者全部热敏元件随部分喷头本体安装于吊顶下",{"key":22,"text":23,"correct":14},"D","边墙型喷头根据选定的型号、规格，水平安装于顶棚下的边墙上，或者直立向上、下垂安装于顶棚下",{"key":25,"text":26,"correct":27},"E","下垂型喷头连接DN25 mm的短立管或者直接向上直立安装于配水支管上",false,"ABCD","不同类型的喷头按照下列要求安装：（1）直立型喷头连接DN25 mm短立管或者直接向上直立安装于配水支管上。（2）下垂型喷头连接DN25 mm的短立管或者直接下垂安装于配水支管上。（3）边墙型喷头根据选定的型号、规格，水平安装于顶棚（吊顶）下的边墙上，或者直立向上、下垂安装于顶棚下的边墙上。（4）干式喷头连接于特殊的短立管上，根据其保护区域结构特征和喷头型号、规格，直立向上、下垂或者水平安装于配水支管上，短立管入口处设置密封件，阻止水流在喷头动作前进入立管。（5）嵌入式喷头、隐蔽式喷头安装时，喷头根部螺纹及其部分或者全部本体嵌入吊顶护罩内，喷头下垂安装于配水支管上。（6）齐平式喷头安装时，喷头根部螺纹及其部分本体下垂安装于吊顶内配水支管上，部分或者全部热敏元件随部分喷头本体安装于吊顶下。（7）喷头安装在易受机械损伤处，加设喷头防护罩。",{"id":6,"name":31,"category":32,"favorite":33},"消防技术综合能力(一级、二级)","建筑工程",0]