[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-936003":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},936003,605,2,"多选题","对自动喷水灭火系统的干式报警阀组进行检查，下列关于干式报警阀组的安装方法中，符合规范要求的有（ ）。",[11,15,18,22,25],{"key":12,"text":13,"correct":14},"A","干式报警阀组宜安装在不发生冰冻的场所",true,{"key":16,"text":17,"correct":14},"B","低气压预报警装置安装在配水干管一侧",{"key":19,"text":20,"correct":21},"C","充气连接管路的接口安装在报警阀气室充注水位以上部位，充气连接管道的直径为13 mm",false,{"key":23,"text":24,"correct":14},"D","安装完成后，向报警阀气室注入高度为80 mm的清水",{"key":26,"text":27,"correct":14},"E","安全排气阀安装在气源与报警阀组之间，靠近报警阀组一侧","ABDE","自动喷水灭火系统中干式报警阀组安装及技术检测要求如下：（1）安装在不发生冰冻的场所。（2）安装完成后，向报警阀气室注入高度为50～100 mm的清水。（3）充气连接管路的接口安装在报警阀气室充注水位以上部位，充气连接管道的直径不得小于15mm；止回阀、截止阀安装在充气连接管路上。（4）按照消防设计文件要求安装气源设备，符合现行国家相关技术标准的规定。（5）安全排气阀安装在气源与报警阀组之间，靠近报警阀组一侧。（6）加速器安装在靠近报警阀的位置，设有防止水流进入加速器的措施。（7）低气压预报警装置安装在配水干管一侧。（8）报警阀充水一侧和充气一侧、空气压缩机的气泵和储气罐以及加速器等部位分别安装监控用压力表；管网充气压力符合消防设计文件的规定值。",{"id":6,"name":31,"category":32,"favorite":33},"消防技术综合能力(一级、二级)","建筑工程",0]