[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-936002":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},936002,605,2,"多选题","自动喷水灭火系统施工前对到场的400只闭式喷头进行密封性能试验，正确的做法有（ ）。",[11,15,18,22,25],{"key":12,"text":13,"correct":14},"A","密封性能试验的试验压力为3．0 MPa",true,{"key":16,"text":17,"correct":14},"B","密封性能试验的保压时间为5 min",{"key":19,"text":20,"correct":21},"C","随机从到场喷头中抽取1％，共4只作为试验喷头",false,{"key":23,"text":24,"correct":21},"D","当1只喷头试验不合格时，再抽取2％，共8只的到场喷头进行重复试验",{"key":26,"text":27,"correct":14},"E","累计2只喷头试验不合格时，拒绝使用该批喷头","ABE","闭式喷头密封性能试验检查要求如下：（1）密封性能试验的试验压力为3．0 MPa，保压时间不少于3 min。（2）随机从每批到场喷头中抽取1％，且不少于5只作为试验喷头。当1只喷头试验不合格时，再抽取2％，且不少于10只的到场喷头进行重复试验。（3）试验以喷头无渗漏、无损伤判定为合格。累计2只以及2只以上喷头试验不合格的，不得使用该批喷头。",{"id":6,"name":31,"category":32,"favorite":33},"消防技术综合能力(一级、二级)","建筑工程",0]