[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-935995":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":22,"analysis":25},935995,605,1,"单选题","下列关于喷头选型的说法，错误的是（ ）。",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","顶板为水平面的医院病房内采用边墙型喷头",false,{"key":16,"text":17,"correct":14},"B","预作用系统采用干式下垂型喷头",{"key":19,"text":20,"correct":14},"C","地下商场采用RTI=50（m·s）0．5的喷头",{"key":22,"text":23,"correct":24},"D","自动喷水防护冷却系统不应采用边墙型洒水喷头",true,"根据《自动喷水灭火系统设计规范》GB 50084—2017中6．1．3—3，顶板为水平面的轻危险级、中危险级I级住宅建筑、宿舍、旅馆建筑客房、医疗建筑病房和办公室，可采用边墙型洒水喷头，A选项正确；根据6．1．4，干式系统、预作用系统应采用直立型喷头或干式下垂型喷头，B选项正确；根据6．1．7—4，地下商业场所宜采用快速响应喷头，C选项正确；根据6．1．6，自动喷水防护冷却系统可采用边墙型洒水喷头，D选项错误。本题答案为D。",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]