[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-935991":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":16,"analysis":25},935991,605,1,"单选题","下列有关水力警铃验收测试时的说法，正确的是（ ）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","水力警铃喷嘴处压力不应小于0．05MPa，且距水力警铃2m远处警铃声声强不应小于65dB",false,{"key":16,"text":17,"correct":18},"B","水力警铃喷嘴处压力不应小于0．05MPa，且距水力警铃3m远处警铃声声强不应小于70dB",true,{"key":20,"text":21,"correct":14},"C","水力警铃喷嘴处压力不小于0．1MPa，且距水力警铃3m远处警铃声声强不应小于70dB",{"key":23,"text":24,"correct":14},"D","水力警铃喷嘴处压力不大于0．1MPa，且距水力警铃2m远处警铃声声强不应小于65dB","根据《自动喷水灭火系统施工及验收规范》GB 50261—20178．0．7—3，水力警铃的设置位置应正确。测试时，水力警铃喷嘴处压力不应小于0．05MPa，且距水力警铃3m远处警铃声声强不应小于70dB；本题答案为B。",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]