[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-935988":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":16,"analysis":25},935988,605,1,"单选题","某消防技术服务机构对某单位设置的自动喷水灭火系统进行年度检测时发现，打开末端试水装置，达到规定的流量时水流指示器动作并发出信号，报警阀打开，压力开关正常动作，但水力警铃不响。对出现这种故障的原因进行分析，则原因最有可能是（ ）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","报警管路延迟器堵塞",false,{"key":16,"text":17,"correct":18},"B","水力警铃铃锤被卡住",true,{"key":20,"text":21,"correct":14},"C","报警管路堵塞",{"key":23,"text":24,"correct":14},"D","报警阀漏水","水力警铃工作不正常（不响、响度不够、不能持续报警）故障原因分析：1）产品质量问题或者安装调试不符合要求；2）控制口阻塞或者铃锤机构被卡住；根据题意，压力开关正常动作，说明压力开关之前的管路没有问题。本题答案为B。",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]