[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-935987":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},935987,605,1,"单选题","某单位自动喷水系统竣工后，建设单位进行工程验收，根据现行国家标准《自动喷水灭火系统施工及验收规范》GB 50261—2017要求，系统管网组件验收时，需要全数检查的是（ ）。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","水流指示器",false,{"key":16,"text":17,"correct":14},"B","信号阀",{"key":19,"text":20,"correct":21},"C","减压阀",true,{"key":23,"text":24,"correct":14},"D","减压孔板","根据《自动喷水灭火系统施工及验收规范》GB 50261—20178．0．8—4，管网不同部位安装的报警阀组、闸阀、止回阀、电磁阀、信号阀、水流指示器、减压孔板、节流管、减压阀、柔性接头、排水管、排气阀、泄压阀等，均应符合设计要求；检查数量：报警阀组、压力开关、止回阀、减压阀、泄压阀、电磁阀全数检查，合格率应为100％；闸阀、信号阀、水流指示器、减压孔板、节流管、柔性接头、排气阀等抽查设计数量的30％，数量均不少于5个，合格率应为100％。本题答案为C。",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]