[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-935984":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},935984,605,1,"单选题","某消防工程施工单位对安装完成的湿式自动喷水灭火系统进行检测，检测结果如下，其中不符合现行国家技术标准的是（ ）。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","打开末端试水装置，水泵在3min内启动",false,{"key":16,"text":17,"correct":14},"B","按下手动控制盘上启泵按钮，消防水泵在50s内投入正常运行",{"key":19,"text":20,"correct":21},"C","以备用泵切换启动消防水泵时，消防水泵在5min内投入使用",true,{"key":23,"text":24,"correct":14},"D","消防水泵停泵时，水锤消除设施后的压力为水泵出口额定压力的1．2倍","根据《自动喷水灭火系统施工及验收规范》GB 50261—20178．0．6—3，湿式自动喷水灭火系统的最不利点做末端放水试验时，自放水开始至水泵启动时间不应超过5min．A选项正确；根据8．0．6—4，自动或手动启动消防泵时应在55s内投入正常运行，B选项正确；根据7．2．3—2，以备用电源切换方式或备用泵切换启动消防水泵时，消防水泵应在1min或2min内投入使用，C选项错误；根据8．0．6—5，消防水泵停泵时，水锤消除设施后的压力不应超过水泵出口额定压力的1．3～1．5倍，D选项正确。本题答案为C。",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]