[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-935982":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":12,"analysis":25},935982,605,1,"单选题","在湿式自动喷水灭火系统中，过滤器安装在报警水流管路上时，应安装在（ ）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","延迟器前",true,{"key":16,"text":17,"correct":18},"B","延迟器后",false,{"key":20,"text":21,"correct":18},"C","压力开关后",{"key":23,"text":24,"correct":18},"D","水力警铃后","根据《自动喷水灭火系统施工及验收规范》GB 50261—20175．3．3，湿式报警阀组的安装应符合下列要求： 1）应使报警阀前后的管道中能顺利充满水；压力波动时，水力警铃不应发生误报警。 2）报警水流通路上的过滤器应安装在延迟器前，且便于排渣操作的位置。 本题答案为A。",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]