[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-935977":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":22,"analysis":25},935977,605,1,"单选题","对水流指示器进行现场功能性检查，当试验压力为1．0MPa，流量达到（ ）L／min时，必须报警。",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","15",false,{"key":16,"text":17,"correct":14},"B","20",{"key":19,"text":20,"correct":14},"C","27．5",{"key":22,"text":23,"correct":24},"D","37．5",true,"根据《自动喷水灭火系统》GB 5135—2003第7部分：水流指示器，5．8．1，检查水流指示器灵敏度，试验压力为0．14MPa～1．2MPa，流量不大于15．0L／min时，水流指示器不报警；流量在15．0L／min～37．5L／min任一数值时，可报警可不报警；到达37．5L／min必须报警。本题答案为D。",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]