[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-935970":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},935970,605,2,"多选题","对自动喷水灭火系统进行水压试验，根据现行国家标准《自动喷水灭火系统施工及验收规范》GB 50261—2017，下列关于水压试验要求的说法中，正确的是（ ）。",[11,15,18,22,25],{"key":12,"text":13,"correct":14},"A","水压试验时环境温度不宜低于4℃",false,{"key":16,"text":17,"correct":14},"B","水压强度试验的测试点应设在系统管网的压力最不利点",{"key":19,"text":20,"correct":21},"C","对管网注水时应将管网内的空气排净，并应缓慢升压，达到试验压力后稳压30min后，管网应无泄漏、无变形，且压力降不应大于0．05MPa",true,{"key":23,"text":24,"correct":21},"D","自动喷水灭火系统的水源干管、进户管和室内埋地管道，应在回填前单独或与系统一起进行水压强度试验和水压严密性试验",{"key":26,"text":27,"correct":14},"E","水压严密性试验应在水压强度试验和管网冲洗合格后进行，试验压力应为设计工作压力，稳压24h，压力降不应大于0．01Mpa","CD","根据《自动喷水灭火系统施工及验收规范》GB 50084—2017:6．2．4，水压试验时环境温度不宜低于5℃，当低于5℃时，水压试验应采取防冻措施，A选项错误；根据6．2．2，水压强度试验的测试点应设在系统管网的最低点。对管网注水时应将管网内的空气排净，并应缓慢升压，达到试验压力后稳压30min后，管网应无泄漏、无变形，且压力降不应大于0．05MPa，B选项错误，C选项正确；根据6．2．5，自动喷水灭火系统的水源干管、进户管和室内埋地管道，应在回填前单独或与系统一起进行水压强度试验和水压严密性试验，D选项正确：根据6．2．3，水压严密性试验应在水压强度试验和管网冲洗合格后进行。试验压力应为设计工作压力，稳压24h，应无泄漏，E选项错误。本题答案为CD。",{"id":6,"name":31,"category":32,"favorite":33},"消防技术综合能力(一级、二级)","建筑工程",0]