[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-935968":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},935968,605,2,"多选题","根据现行国家消防技术标准，对投入使用的自动喷水灭火系统需要每月进行检查维护的内容有（ ）。",[11,15,18,22,25],{"key":12,"text":13,"correct":14},"A","对控制阀门的铅封、锁链进行检查",true,{"key":16,"text":17,"correct":14},"B","消防水泵启动运转",{"key":19,"text":20,"correct":21},"C","对水源控制阀、报警阀组进行外观检查",false,{"key":23,"text":24,"correct":21},"D","利用末端试水装置对进行放水试验",{"key":26,"text":27,"correct":14},"E","检查电磁阀并做启动试验","ABE","对自动喷水灭火系统进行周期性检查维护时，下列项目至少每月进行一次：（1）电动、内燃机驱动的消防水泵（稳压泵）启动运行测试。（2）喷头完好状况、备用量及异物清除等检查。（3）系统所有阀门状态及其铅封、锁链完好状况检查。（4）消防气压给水设备的气压、水位测试，消防水池、消防水箱的水位以及消防用水不被挪用的技术措施。（5）水泵接合器完好性检查。（6）过滤器排渣、完好状况检查。（7）报警阀启动性能测试。（8）电磁阀启动试验。根据《自动喷水灭火系统施工及验收规范》（GB50261），自动喷水灭火系统维护管理工作检查项目中水源控制阀、报警阀组进行外观检查为每日检查项目。",{"id":6,"name":31,"category":32,"favorite":33},"消防技术综合能力(一级、二级)","建筑工程",0]