[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-935965":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},935965,605,2,"多选题","某消防技术服务机构对已完工的湿式自动喷水灭火系统进行竣工验收检查，检查结果符合现行国家工程建设消防技术标准的是（ ）。",[11,15,19,22,25],{"key":12,"text":13,"correct":14},"A","在吊顶下安装了下垂型洒水喷头",true,{"key":16,"text":17,"correct":18},"B","通透面积占吊顶总面积的比例为80的场所，喷头安装在吊顶的下方",false,{"key":20,"text":21,"correct":14},"C","喷头备用品数量为20只，为安装喷头总数的1％",{"key":23,"text":24,"correct":18},"D","末端试水装置采用管道与排水管道直接相连",{"key":26,"text":27,"correct":18},"E","压力开关垂直安装于延迟器后面的竖向管道上","AC","根据《自动喷水灭火系统设计规范》GB 50084—20176．1．3，湿式系统的洒水喷头在吊顶下布置时，应采用下垂型洒水喷头或吊顶型洒水喷头，A选项正确； 根据7．1．13，当通透面积占吊顶总面积的比例为大于70％时，喷头应设置在吊顶上方，B选项错误； 根据6．1．10，自动喷水灭火系统应有备用洒水喷头，其数量不应少于总数的1％，且每种型号均不得少于10只，C选项正确； 根据6．5．2，末端试水装置的出水，应采取孔口出流的方式排入排水管道，D选项错误； 根据《自动喷水灭火系统施工及验收规范》GB 50261—20175．4．3，压力开关应竖直安装在通往水力警铃的管道上，且不应在安装中拆装改动，E选项错误。本题答案为AC。",{"id":6,"name":31,"category":32,"favorite":33},"消防技术综合能力(一级、二级)","建筑工程",0]