[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-935964":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},935964,605,2,"多选题","自动喷水灭火系统因建筑高差较大造成的超压，通常在系统相应管段上安装设置（ ）以控制管道动压。",[11,15,18,22,25],{"key":12,"text":13,"correct":14},"A","减压孔板",true,{"key":16,"text":17,"correct":14},"B","节流管",{"key":19,"text":20,"correct":21},"C","减压阀",false,{"key":23,"text":24,"correct":21},"D","止回阀",{"key":26,"text":27,"correct":21},"E","报警阀","AB","自动喷水灭火系统由洒水喷头、水流报警装置（水流指示器、压力开关）、报警阀组等组件，以及管道、供水设施组成；为便于正常使用、检修维护，通常还在系统中设置泄水阀（泄水口）、排气阀（排气口）和排污口；为控制因建筑高差较大造成的超压，通常采用分区供水或者在系统相应管段上安装减压阀，以控制管道静压；通常在系统相应管段上安装设置减压孔板或者节流管，以控制管道动压。本题答案为AB。",{"id":6,"name":31,"category":32,"favorite":33},"消防技术综合能力(一级、二级)","建筑工程",0]