[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-935958":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},935958,605,1,"单选题","根据现行国家标准《自动喷水灭火系统施工及验收规范》G350261—2017，对自动喷水灭火系统的报警阀进行验收，下列关于自动喷水灭火系统管道充水时间的要求中，正确的是（ ）。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","干式系统配水管道充水时间不宜大于2min",false,{"key":16,"text":17,"correct":14},"B","由火灾自动报警系统和充气管道上设置的压力开关开启预作用装置的预作用系统，其管道充水时间不宜大于2min",{"key":19,"text":20,"correct":21},"C","雨淋系统的配水管道充水时间不宜大于2min",true,{"key":23,"text":24,"correct":14},"D","仅由火灾自动报警系统联动开启预作用装置的预作用系统，其配水管道充水时间不宜大于1min","根据《自动喷水灭火系统施工及验收规范》GB 50261—20178．0．8—5，干式系统、由火灾自动报警系统和充气管道上设置的压力开关开启预作用装置的预作用系统，其配水管道充水时间不宜大于1min；雨淋系统和仅由水灾自动报警系统联动开启预作用装置的预作用系统，其配水管道充水时间不宜大于2min。本题答案为C。",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]