[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-935957":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},935957,605,1,"单选题","对某商业中心内多栋建筑的自动喷水灭火系统进行检查，下列检查结果中不符合规范要求的是（ ）。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","末端试水装置的连接管管径为25mm",false,{"key":16,"text":17,"correct":14},"B","干式自动喷水灭火系统的供气管道采用钢管，管径为15mm",{"key":19,"text":20,"correct":21},"C","短立管的管径为20mm",true,{"key":23,"text":24,"correct":14},"D","预作用系统的供气管道采用铜管，管径为10mm","根据《自动喷水灭火系统设计规范》GB 50084—20178．0．10，短立管及末端试水装置的连接管，其管径不应小于25mm，A选项正确，C选项错误；根据8．0．12，干式系统、预作用系统的供气管道，采用钢管时，管径不宜小于15mm，采用铜管时，管径不宜小于10mm，BD选项正确。本题答案为C。",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]