[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-935956":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":22,"analysis":25},935956,605,1,"单选题","下列关于自动喷水灭火系统组件安装的说法，错误的是（ ）。",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","报警阀和水力警铃的连接管当采用公称直径20mm的镀锌钢管时，长度不应超过20m",false,{"key":16,"text":17,"correct":14},"B","信号阀和水流指示器之间的间距不宜小于300mm",{"key":19,"text":20,"correct":14},"C","报警阀前的可调式减压阀宜水平安装，阀盖向上",{"key":22,"text":23,"correct":24},"D","干式报警阀充气管路上安全排气阀应安装在气源与报警阀之间，且应靠近气源侧",true,"根据《自动喷水灭火系统施工及验收规范》GB 50261—20175．4．4，水力警铃和报警阀的连接应采用热镀锌钢管，当镀锌钢管的公称直径为20mm时，其长度不宜大于20m，A选项正确；根据5．4．6，信号阀应安装在水流指示器前的管道上，与水流指示器之间的距离不宜小于300mm，B选项正确；根据5．4．10—5，可调式减压阀宜水平安装，阀盖应向上，C选项正确；根据5．3．4—5，安全排气阀应安装在气源与报警阀之间，且应靠近报警阀，D选项错误。本题答案为D。",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]