[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-935954":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},935954,605,1,"单选题","某综合楼的自动喷水灭火系统的设计工作压力为1．1 MPa，消防工程施工单位对系统的管道进行水压试验，则该系统的水压强度试验不应低于（ ）MPa。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","1．65",false,{"key":16,"text":17,"correct":14},"B","1．4",{"key":19,"text":20,"correct":21},"C","1．5",true,{"key":23,"text":24,"correct":14},"D","1．3","根据《自动喷水灭火系统设计规范》GB 50084—20176．2．1，当系统设计工作压力等于或小于1．0MPa时，水压强度试验压力应为设计工作压力的1．5倍，并不应低于1．4MPa；当系统设计工作压力大于1．0MPa时，水压强度试验压力应为该工作压力加0．4MPa。本题答案为C。",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]