[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-935953":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":16,"analysis":25},935953,605,1,"单选题","对湿式自动喷水灭火系统进行年度检测，打开某个防火分区的试水阀，水流指示器和压力开关均未动作，消防水泵也未启动，现场检查压力开关和水流指示器及消防水泵均正常，出现这种情况的原因最有可能的是（ ）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","水泵控制柜未设定在“自动”状态",false,{"key":16,"text":17,"correct":18},"B","水流指示器前的信号蝶阀关闭",true,{"key":20,"text":21,"correct":14},"C","报警管路控制阀关闭",{"key":23,"text":24,"correct":14},"D","消防联动控制器处于手动状态","根据系统工作原理，水流指示器前信号蝶阀关闭，打开该支路试水阀，水流指示器、压力开关等系统组件均不动作。",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]