[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-935943":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},935943,605,2,"多选题","下列关于内扣式消防接口的抗跌落性能检测说法中，正确的有（ ）。",[11,15,19,22,25],{"key":12,"text":13,"correct":14},"A","内扣式接口以扣爪垂直朝上的位置，接口的最低点离地面（2．0±0．05）m高度自由跌落",false,{"key":16,"text":17,"correct":18},"B","内扣式接口以扣爪垂直朝下的位置，接口的最低点离地面（1．5±0．05）m高度自由跌落",true,{"key":20,"text":21,"correct":14},"C","需反复进行2次",{"key":23,"text":24,"correct":18},"D","需反复进行5次",{"key":26,"text":27,"correct":14},"E","需反复进行3次","BD","内扣式接口以扣爪垂直朝下的位置，将接口的最低点离地面（1．5±0．05）m高度，然后自由跌落到混凝土地面上。反复进行5次后，检查接口是否有断裂现象，并进行操作，如消防接口跌落后出现断裂或不能正常操纵使用的，则判该产品为不合格。卡式接口和螺纹式接口从接口的轴线呈水平状态，将接口的最低点离地面（1．5±0．05）m高度，然后自由跌落到混凝土地面上。反复进行5次后，检查接口是否断裂现象，并进行操作，如消防接口跌落后出现断裂或不能正常操纵使用的，则判该产品为不合格。本题答案为BD。",{"id":6,"name":31,"category":32,"favorite":33},"消防技术综合能力(一级、二级)","建筑工程",0]