[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-935924":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":22,"analysis":25},935924,605,1,"单选题","某建筑安装的室内消火栓系统的设计工作压力为0．8MPa，现在对此系统给水网管进行水压测试。检测人员的下列做法中，错误的是（ ）。",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","水压强度试验的试验压力为1．4MPa",false,{"key":16,"text":17,"correct":14},"B","水压强度试验的测试点设在系统管网的最低点",{"key":19,"text":20,"correct":14},"C","对管网注水时，应将管网内的空气排净，缓慢升压，达到试验压力后，稳压30min后观察管网的泄露变形情况",{"key":22,"text":23,"correct":24},"D","进行水压严密性试验的试验压力为0．8MPa，稳压12h后观察泄露情况",true,"水压严密性试验在水压强度试验和管网冲洗合格后进行。试验压力为设计工作压力，稳压24h，应无泄漏。",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]