[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-935898":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":16,"analysis":25},935898,605,1,"单选题","对某建筑内安装完毕的室内消火栓系统进行验收，下列验收结果中，符合相关规范规定的是（ ）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","建筑物内设置的消火栓只能采用同一品牌",false,{"key":16,"text":17,"correct":18},"B","水泵控制柜打在自动状态，按下水泵控制柜上的启动按钮，水泵启动",true,{"key":20,"text":21,"correct":14},"C","设有试验用消火栓，但栓口处未设置压力表",{"key":23,"text":24,"correct":14},"D","消火栓栓口中心距地面的高度为1．1m，并设置在靠近门轴的一侧","根据《消防给水及消火栓系统技术规范》GB 50974—201412．3．9—1，室内消火栓的选型、规格应符合设计要求，规范并未对消火栓的品牌作出要求，A选项错误；水泵控制柜打在自动状态，按下水泵控制柜上的启动按钮，水泵启动，B选项正确；根据12．3．9—3，试验用消火栓栓口处应设置压力表，C选项错误；根据12．3．9—7，消火栓栓口不应安装在门轴侧，D选项错误。本题答案为B。",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]