[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-935896":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":16,"analysis":25},935896,605,1,"单选题","根据《消防给水及消火栓系统技术规范》（GB 50974）的规定，下列日常维护管理正确的是（ ）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","每年应监测市政给水管网的压力和供水能力",false,{"key":16,"text":17,"correct":18},"B","每季度应该对消火栓进行一次外观和漏水检查，发现有不正常的消火栓应及时更换",true,{"key":20,"text":21,"correct":14},"C","在冬季每月应对消防储水设施进行室内温度和水温检测，当结冰或室内温度低于5℃时，应采取确保不结冰和室温不低于5℃的措施",{"key":23,"text":24,"correct":14},"D","每季度应该对消火栓进行一次水压强度试验检查，发现有不正常的消火栓应及时更换","室外阀门井中，进水管上的控制阀门应每个季度检查一次，核实其处于全开启状态。系统上所有的控制阀门均应采用铅封或锁链固定在开启或规定的状态。每月应对铅封、锁链进行一次检查，当有破坏或损坏时应及时修理更换。根据《消防给水及消火栓系统技术规范》（GB 50974），每季度对消火栓进行一次外观和漏水检查，发现有不正常的消火栓应及时更换。每季应监测市政给水管网的压力和供水能力。在冬季每天应对消防储水设施进行室内温度和水温检测，当结冰或室内温度低于5℃时，应采取确保不结冰和室温不低于5℃的措施。",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]