[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-935892":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},935892,605,2,"多选题","某商业中心有五栋建筑，分别为 A、 B、 C、 D、 E，五栋建筑均采用消防水泵串联分区供水形式，分高、低两个分区，维保单位对该商业中心进行检查，下列检查不符合规范要求的是（ ）。",[11,15,18,21,25],{"key":12,"text":13,"correct":14},"A","建筑采用消防水泵直接串联分区供水，检测时消防水泵从高区到低区依次顺序启动",true,{"key":16,"text":17,"correct":14},"B","建筑采用消防水泵直接串联分区供水，在串联消防水泵吸水管上设置了减压型倒流防止器",{"key":19,"text":20,"correct":14},"C","中间转输水箱的有效储水容积为18m3",{"key":22,"text":23,"correct":24},"D","转输水箱兼做低区的高位消防水箱",false,{"key":26,"text":27,"correct":24},"E","串联转输水箱的溢流管连接到底部的消防水池","ABC","根据《消防给水及消火栓系统技术规范》GB 50974—20146．2．3—3，当采用消防水泵直接串联时，应采取确保供水可靠性的措施，且消防水泵从低区到高区应能依次顺序启动，A选项错误；根据6．2．3—4，当采用消防水泵直接串联时，应校核系统供水压力，并应在串联消防水泵出水管上设置减压型倒流防止器，B选项错误；根据6．2．3—1，当采用消防水泵转输水箱串联时，转输水箱的有效储水容积不应小于60m3，转输水箱可作为高位消防水箱，C选项错误，D选项正确；根据6．2．3—2，串联转输水箱的溢流管宜连接到消防水池，E选项正确。本题答案为ABC。",{"id":6,"name":31,"category":32,"favorite":33},"消防技术综合能力(一级、二级)","建筑工程",0]