[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-935888":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},935888,605,2,"多选题","某建筑，室内消防采用临时高压消防给水系统联合供水，室外供水管道采用DN200球墨铸铁管道，埋地敷设，长度为3000m。经检测，室外管网漏水率为3．6L／（min·km），室内管网漏水量为0．2L／s，则该系统管网总泄漏量和稳压泵设计流量正确的有（ ）。",[11,15,19,22,25],{"key":12,"text":13,"correct":14},"A","管网泄漏量0．38L／s，稳压泵设计流量1 L／s",true,{"key":16,"text":17,"correct":18},"B","管网泄漏量0．20L／s，稳压泵设计流量0．79L／s",false,{"key":20,"text":21,"correct":18},"C","管网泄漏量0．38L／s，稳压泵设计流量0．56L／s",{"key":23,"text":24,"correct":14},"D","管网泄漏量0．38L／s，稳压泵设计流量1．5L／s",{"key":26,"text":27,"correct":18},"E","管网泄漏量0．20L／s，稳压泵设计流量1L／s","AD","由于该建筑室外管网的总长度为3km，漏水率为3．6L／（min·km），其泄漏量应为3×3．6÷60=0．18 L／s，故该系统管网总泄漏量为0．18+0．2=0．38 L／s，BE选项错误；稳压泵的设计流量不宜小于1L／s，C选项错误。本题答案为AD。",{"id":6,"name":31,"category":32,"favorite":33},"消防技术综合能力(一级、二级)","建筑工程",0]