[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-935884":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":22,"analysis":25},935884,605,1,"单选题","某办公楼建筑采用临时高压消防给水系统,屋顶设有高位消防水箱和增压稳压设施。下列关于系统维护管理,不正确的是（ ）。",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","每日对稳压泵的停泵启泵压力和启泵次数等进行检查和记录运行情况",false,{"key":16,"text":17,"correct":14},"B","每月对气压水罐的压力和有效容积等进行一次检测",{"key":19,"text":20,"correct":14},"C","每季度对消防水泵的出流量和压力进行一次试验",{"key":22,"text":23,"correct":24},"D","每季度对电动阀和电磁阀的供电和启闭性能进行检测",true,"给水管网的维护管理： （1）系统上所有的控制阀门均应采用铅封或锁链固定在开启或规定的状态，每月应对铅封、锁链进行一次检查，当有破坏或损坏时应及时修理更换。 （2）每月应对电动阀和电磁阀的供电和启闭性能进行检测。",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]