[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-935881":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":12,"analysis":25},935881,605,1,"单选题","对自动喷水灭火系统的组件进行调试，根据现行国家标准《自动喷水灭火系统施工及验收规范》GB 50261—2017，下列关于系统组件调试的要求说法中，不正确的是（ ）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","以手动方式启动消防水泵时，消防水泵应在30s内投入正常运行",true,{"key":16,"text":17,"correct":18},"B","以备用泵切换启动消防水泵时，消防水泵应在2min内投入正常运行",false,{"key":20,"text":21,"correct":18},"C","稳压泵应能自动启停",{"key":23,"text":24,"correct":18},"D","以备用电源切换方式启动消防水泵时，消防水泵应在1min内投入正常运行","根据《自动喷水灭火系统施工及验收规范》GB 50261—2017，7．2．3—1，以自动或手动方式启动消防水泵时，消防水泵应在55s内投入正常运行，A选项错误； 根据7．2．3—2，以备用电源切换方式或备用泵切换启动消防水泵时，消防水泵应在1min或2min内投入正常运行，BD选项正确；根据7．2．4，稳压泵应按设计要求进行调试。当达到设计启动条件时，稳压泵应立即启动；当达到系统设计压力时，稳压泵应自动停止运行，当消防主泵启动时，稳压泵应停止运行，C选项正确。",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]