[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-935861":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},935861,605,2,"多选题","下列关于某建筑内消防水泵的调试情况，不符合规范要求的是（ ）。",[11,15,18,21,25],{"key":12,"text":13,"correct":14},"A","以自动直接启动或手动直接启动消防水泵时，消防水泵在50s内投入正常运行，无不良噪声和振动",false,{"key":16,"text":17,"correct":14},"B","以备用电源切换方式切换启动消防水泵时，消防水泵在50s内正常运行",{"key":19,"text":20,"correct":14},"C","机械应急启动消防水泵时，消防水泵在报警后3．0min内正常工作",{"key":22,"text":23,"correct":24},"D","消防水泵能自动和手动启停",true,{"key":26,"text":27,"correct":24},"E","消防水泵从接到启泵信号到水泵正常运转的自动启动时间为2．5min","DE","A正确，以自动直接启动或手动直接启动消防水泵时，消防水泵应在55s内投入正常运行，且应无不良噪声和振动。B正确，以备用电源切换方式或备用泵切换启动消防水泵时，消防水泵应分别在1min或2min内投入正常运行。C正确，消防水泵控制柜应设置机械应急启泵功能，并应保证在控制柜内的控制线路发生故障时由有管理权限的人员在紧急时启动消防水泵。机械应急启动时，应确保消防水泵在报警后5．0min内正常工作。D错，消防水泵应能手动启停和自动启动。E错，消防水泵应确保从接到启泵信号到水泵正常运转的自动启动时间不应大于2min。",{"id":6,"name":31,"category":32,"favorite":33},"消防技术综合能力(一级、二级)","建筑工程",0]